HZGPNYT 3KVA/5KV power frequency withstand voltage test transformer
I. Overview
HZGPNYT power frequency voltage tester adopts integrated design, small size, light weight, more convenient for transportation and portable operation. The over-current protection of voltage tester is set by current relay, The high-voltage output, direct reading instrument and operation are integrated with the voltage stand. Therefore, the operation is simple, practical and reliable.
II. Basic parameters
1. Capacity: 3KVA
2. Input: AC220V + 10%
3. Output: AC0-5KV
4. Instruments: 0-5KV/100V
5. Setting Current: 15A
6. Weight: about 75Kg
7. Size: 430*500*750mm
III. Use Environment
1. Ambient temperature: 0-40 degrees Celsius
2. Altitude: below 1000M
3. Relative humidity: <85%>85%>
4. Workplaces should be free from chemical dust and explosive media that seriously affect insulation.
IV. MAIN CHARACTERISTICS
The voltage tester consists of contact voltage regulator, control, measurement, protection circuit and test transformer. It is easy to operate and maintain.
V. Outline sketch
1. High Voltage Ammeter 2. High Voltage Meter
3. Power Signal 4. Zero Signal 5. Working Signal 6. Alarm Signal
7. Power supply main switch 8. Voltage withstand time setting
9. Timing switch 10. Voltage Regulator Handle
11. Start Button 12. Stop Button 13. Power input 220V 14. high voltage output
15. Grounding terminal 16. Low Voltage Protection Current Setting
VI. Usage
1. Connect the power cable to the 220V AC power supply, close the main power switch on the right side of the pressure stand, and energize the pressure stand. At this time, the power signal light (green light) is on, and the zero signal light (green light) is also on. If the zero signal light is off, turn the voltage regulator counterclockwise back to the zero position.
2. Press the “Start" button. At this time, the working signal light (red light) is on. Turn the regulator handwheel to rotate clockwise slowly. At the same time, keep an eye on the high voltage voltmeter and stop rotating when you reach the required voltage. Wheel, toggle timing switch, time relay start (pre-set pressure time). When the test time is up, the alarm light on the pressure test bench flashes and an alarm sounds. At the same time, the regulator should be quickly rotated counterclockwise back to zero, and the “stop" button is pressed, the contactor is powered off, and the work signal is off. Turn off the main power switch, release the work connection, and the test is completed.
3. The low-voltage over-current value of the test bench is set to 0~50A, and is set according to the over-current value required for the normal test of the test sample. It is set at 80% of the rated current value at the factory. During the boosting process, if a short-circuit overcurrent occurs during the breakdown short-circuit overcurrent, the power supply should be cut off and the voltage regulator should be turned to zero.
4. The high voltage current and voltage indication of the voltage stand must be grounded reliably during the test. If the grounding is not good, it is forbidden to use.