您好,欢迎来到亚洲制造网!请 |免费注册

产品展厅本站服务收藏该商铺

Huazheng Electric Manufacturing (Baoding) Co.
Ltd

免费会员
手机逛
Huazheng Electric Manufacturing (Baoding) Co.
Ltd
当前位置:Huazheng Electric Manufacturing (Baoding) Co., Ltd>>High Voltage Tester>>DC Hipot Tester>> HZZGF-Z 80kV 5mA Portable DC Hipot Test Set

HZZGF-Z 80kV 5mA Portable DC Hipot Test Set

产品二维码
参  考  价:面议
具体成交价以合同协议为准
  • 产品型号:
  • 品牌:
  • 产品类别:接近开关
  • 所在地:
  • 信息完整度:
  • 样本:
  • 更新时间:2026-03-20 12:48:23
  • 浏览次数:
收藏
举报

联系我时,请告知来自 亚洲制造网

Huazheng Electric Manufacturing (Baoding) Co., Ltd

其他

  • 经营模式:其他
  • 商铺产品:831条
  • 所在地区:
  • 注册时间:2026-03-20
  • 最近登录:2026-03-20
  • 联系人:Julia
  • 电    话:
产品简介

HZZGF-Z 80kV 5ma Portable DC Hipot Test Set Product Completeness 1. Control box 1 2. HV voltage-multiplying cylinder 1 set 3. HV micro-ampere-meter 1 pcs 4. Standard accessories (1) Power line 1 (2) Intermediate frequency output cable 1 (3) Dedicated ground lead 1 (4) Telescopic discharging rod...

详情介绍

HZZGF-Z 80kV 5mA Portable DC Hipot Test Set


Specification

technic parameter

40/4

60/2

60/5

120/2

120/3

120/10

200/2

220/2.5

200/10

300/2

300/3

Rated voltage(KV)

40

60

60

120

120

120

200

220

200

300

300

Rated current(mA)

4

2

5

2

3

10

2

2.5

10

2

3

Rated power(W)

160

120

300

240

360

1200

400

550

2000

600

900

Voltage meter precision

number on voltage meter ±(1.0 %reading±0.2KV)

Current meter precision

number on current meter ±(1.0 %reading±0.2KV)

Ripple coefficient

≤0.5%

Voltage stabilization

stochastic wave ,≤1% when power wave±10%

Overloading ability

overstep 10% of rated voltage when loading nothing for ten minutes; the biggest charge current can be 1.5 times of rated current

Power

single-phase alternating current power of 50HZ 220V±10%

Working

incontinuous use

The time should be no more than 30 minutes when continuously use it

Work condition

temperature:-10~40℃

relative humidity:≤85% when room temperature is 25℃

height above sea level:below1500 meters

Capacitance

capacitance of the tested res is absoluteness

Can be charged with 1.5 times of rated current

Configuration

electric insulated Voltage Multiplier is made of epoxy FRP(Fiberglass-Reinforced Plastics)

Air insulated、without leak

Characteristic of Control box

One button for high precision of 0.75UDC--1mA(precision≤1.0%)is suit to do zinc oxide lightning arrester test

overvoltage protection use dialing code set,be clear at a glance

International standard box withTwo kind of using way(can be take out from the box for using) makes it easy to use.

80kv 10ma dc hipot tester

Product Completeness

1. Control box 1

2. HV voltage-multiplying cylinder 1 set

3. HV micro-ampere-meter 1 pcs

4. Standard accessories

(1) Power line 1

(2) Intermediate frequency output cable 1

(3) Dedicated ground lead 1

(4) Telescopic discharging rod 1

(5) Ground lead for discharging rod 1

(6) Current-limiting resistance 1 pcs

(7) Micro-ampere-meter line 1

(8) HV outgoing line 1

5. Accompanying documents

(1) Operation Manual 1

(2) Ex-factory Inspection Report 1


Safety Warning

● Those operating DC HV generators must be professional staff with electrical and HV test certificate.

● Provisions of Working Regulation of Power Safety should be strictly observed when using the equipment. There should be a clear cut-off point in the working power supply, which should be cut off clearly in case of replacement of test object and wiring.

● Before the test, it is necessary to make the connection of ground leads of tester control box, voltage-multiplying cylinder and sample reliable; the one-point grounding is conducted as shown in Figure 4-5.

● For large-capacitance test objects, a 100Ω/V resistance discharging rod should be used; the case that no discharging rod is passed through but ground lead is directly connected to the test object is prohibited.

Proper method of discharge: Firstly, make the top metal tip of discharging rod gradually close to the test object, then a hissing sound will appear when it comes to a certain distance, indicating that air gap begins to discharge free. When there is no discharge sound, the top tip of the discharging rod can be used to contact the test object for discharging, and finally the ground lead is connected directly to the test object.

● In case of 200kV+ DC HV tests, although testers wear insulated shoes and stand in a safety area, those persons standing nearby will carry different DC potentials due to HV DC ion space electric field distribution. There will be a slight shock occurred in testers when contacting with each other or the grounding body, which is more obvious in dry areas and in winter; however the energy is small and will not generally cause harm to human body.

● In the tests that discharge impact may be possible (test object breakdown), if the voltage rising is controlled by a host computer in a remote control manner, then the mode of isolating source and electrical isolation (optical fiber or radio) should be applied. Otherwise, the discharge impact may cause damage to the host computer instantaneously.