HV Withstand Test Equipment Series Resonant AC Hipot Test System For Cables
Scope of application
According to your company's field test requirements and the latest regulations of the national power test, combined with product design and manufacturing standards, our company recommends a set of variable frequency series resonant high voltage test equipment, the configuration model is HZ3580-9360/300 series resonance test device. By changing the series-parallel combination of the resonant reactor and the secondary winding connection of the excitation transformer, the following AC voltage withstand test requirements for the power cable can be met:
The system configuration meets the AC withstand voltage test requirements for XLPE cables of 220KV, 800mm2, 5km and below. Maximum capacitance: 0.845μF (5*0.169μF/1km/800mm2); test voltage: 220kV; test time: 60min; maximum sample current: 70A; heavy load test frequency: 30Hz;
The system configuration meets the AC withstand voltage test requirements for 66KV, 800mm2, 5km and below XLPE cables. Maximum capacitance: 1.45μF (5*0.29μF/1km/800mm2); test voltage: 78kV; test time: 60min; maximum sample current: 24A; heavy load test frequency: 30Hz;
Solution
| No. | Name | Model /Specification | Quantity |
| 1 | Frequency Power | HZ3580-250 250kW, | 1 unit |
| 2 | Excitation transformer | HZLCB-250/2.5 ,4×2.5kV/25A | 1 unit |
| 3 | Resonant reactor | HZXK-2340/130 130kV/18A/30H | 4 units |
| 4 | Capacitor divider | HZTRF300-0.001 300kV/2nF*2 units | 1 unit |
| 5 | Accessories | Special wiring, base, equalizing ring, aluminum alloy packing box, Rain cover, voltage divider external meter, etc. | 1 set |
Typical test configuration
| sample Configuration And parameters | 220kV/800mm2/ 5km cables | 66kV/800mm2/ 5km cables |
| capacitance=0.845μF | capacitance=1.45μF | |
| Reactor configuration | 2 units in series and 2 units in parallel (33H series has 1.1 times mutual inductance) | 2 units in parallel(7.5H) |
| Excitation transformer connection | Secondary:2 units in series and 2 units in parallel Output:5kV | Secondary:4 units in parallel Output:2.5kV |
| Resonant frequency/Hz | 30-300 | 30-300 |
| Test voltage/kV | 220 | 78 |
| Test current/A | ≤70 | ≤50 |