Frequency Conversion Hv Test Device Cable AC Resonance Test Systems
I, The test object and test requirements
220KV / 25000KVA main transformer neutral point and other electrical equipment test test, capacitance ≤ 0.01uF, test frequency 45-65Hz, test voltage 160kV, test time 1min.
II, The working environment
1. Ambient temperature: -100C -50 0C;
2. Relative humidity: ≤ 90% RH;
3. Altitude: ≤ 1000 meters;
III, The device main technical parameters and functions
1. Rated capacity: 160kVA;
2. Input power: single-phase 220 or three-phase 380V input frequency of 50Hz;
3. Rated voltage: 160kV;
4. Rated current: 1A;
5. Working frequency: 30-300Hz;
6. Device output waveform: sine wave
7. Waveform distortion rate: the output voltage waveform distortion rate ≤ 1%;
8. Working hours: rated load allowed continuous 5min; 1.1 times over-pressure 1 minute;
9. Temperature rise: rated load continuous operation 5min temperature rise ≤ 65K;
10. Quality factors: the device itself Q ≥ 30 (f = 45Hz);
11. Protection: the test object has over-current, over-voltage and flashover protection test (see the frequency conversion power supply section)
12. Measurement accuracy: System RMS 1.5;
IV. Device capacity to determine
The design of four reactor, the single reactor is 40kVA / 40kV / 1A / 110H, the total capacity of the device is 160kVA.
1,220KV / 25000KVA main transformer neutral point and other electrical equipment test, capacitance ≤ 0.02uF, test frequency 45-65Hz, test voltage 160kV, test time 1min.
Use four reactors in series (coefficient 1.1), then L = 110 * 4 * 1.2 = 528H, with a 160kV / 5000pF compensation capacitor, then:
Test frequency: f = 1 / 2π√ LC = 1 / (2 × 3.14 × √528 × 0.015 × 10 -6) = 56.55 Hz
Test current: I = 2πfCU test = 2π × 56.55 × 0.015 × 10-6 × 160 × 103 = 0.85A
Installation capacity of 160kVA / 160kV, divided into four sections of the reactor, the reactor section for the 40kVA / 40kV / 1A / 110H, the use of reactors in series and parallel can meet the test requirements of the test object.
Test equipment used when the relationship list
Equipment Test | Reactor 40kVA / 40kV four sections | Incentive transformer Output selection |
220KV/25000KVA Main transformer neutral point | Use four series reactors and compensation capacitors | 10kV |