HZJD-2 Transformer Oil Tan Delta Tester
HZJD-2 Transformer Oil Tan Delta Tester Introduction
1.The test cell used of the three-electrode structure in line with the international standard IEC, with electrode spacing 2mm, can eliminate the effects of the stray capacitance and leakage on dielectric loss test results. The apparatus is equipped with the oil drainage solenoid switch, and we can empty the test cell in case of not removing it and rinse it with the test sample.
2.The instrument adopts the medium frequency induction heating, PID temperature control algorithm. This heating method has the advantages of t non-contact between the test cell and the heating body, even heating, fast speed, convenient control, strict control of the temperature within error range of the preset temperature.
3.Internal standard capacitor is SF6 gas-filled three-electrode capacitance, and its capacitor dielectric loss and electrical capacity is independent of ambient temperature, humidity and other effects, so that the instrument accuracy can be ensured even after prolonged use.
4.AC test power supply using AC-DC-AC conversion, effectively avoid the fluctuations in mains voltage and frequency on dielectric loss measurement accuracy effect. Even a generator, the instrument can work properly.
5.Perfect protection function; When there is over voltage、over current or high-voltage short circuit, instruments can quickly cut off pressure, and issues a warning message. When the temperature of the sensor failure or not connected, the instrument will also issue a warning message.
6.There is a temperature limiting relay in the medium frequency induction heating furnace. When temperature above 120 degrees, the instrument frees the relay and stops heating.
7.More convenient the experimental parameter is set. Temperature setting range 0~125℃ , AC voltage setting range 500~2200V, DC voltage setting range 0~500V.
8.Using of large-screen LCD display, with backlight and clear display. Friendly interface, simply follow the Chinese menu prompt, enter the command, the instrument can be automatically tested. And automatically store and print test results.
9.Built-in real-time clock, the test date and time may be saved, displayed and printed with the test results.
10.Calibration functions of cleaned dry cell. The measurement of dry cells capacitance and dielectric loss factor can determine its cleaning and assembly conditions. The calibration data is automatically saved and so that it facilitates the calculation of relative permittivity and DC resistivity.
HZJD-2 Transformer Oil Tan Delta Tester MAJOR TECHNICAL INDICATORS
Voltage supply: AC 220V±10%
Power frequency: 50Hz/60Hz ±1%
Measuring range:
Electric capacity 5pF~200pF
Relative Permittivity 1.000~30.000
Dielectric loss factor 0.00001~100
DC Resistivity 2.5MΩ;m~20TΩ;m
Measuring accuracy:
Electric capacity ± (1% of measured value+0.5pF)
Relative Permittivity ±1% of measured value
Dielectric dissipation factor ± (1% of measured value+0.0001)
DC Resistivity ±10% of measured value
Resolution:
Electric capacity 0.01pF
Relative capacitivity 0.001
Dielectric dissipation factor 0.00001
Measured temperature range:0~125℃
Temperature measurement error:±0.5℃
Test Voltage AC(RMS): 500~2200V Continuously adjustable, frequency 50Hz
Test Voltage DC: 0~500V Continuously adjustable
Power consumption:100W
dimensions: 500×360×420
weight: 22Kg
3.HZJD-2 Transformer Oil Tan Delta Tester USE CONDITIONS
Ambient temperature:0℃ ~40℃ Relative humidity(RH):<>
Solvent cleaning method ⑴ Dismantle the test cell.
⑵ Wash all parts with solvents, and change the solvents.
⑶ Wash all parts with the acetone first, then tap water. Then clean them with distilled water.
⑷ Dry the parts 60~90 minutes in the oven at temperature of 105~110℃.
When testing a group of similar liquid samples but not used, as long as the last test sample has better performance than the specified value of the measuring, we can use the same test cell without intermediate washing. If the performance of the tested sample is inferior to the measuring sample, the test cell must be cleaned before you do the next test
CE Certificate

FAQ
1.What's the warranty?
Normally 12 months
2.Does the power supply can customized?
YES ,if you need customized power supply,pls tell us when you put the order.
3.What's the production time?
Usually 20 days for production, some equipments need extra time to debug.
4.What's the Dlivery method ?
Light-weight cargo is usually by express , Air transport and sea shipping is acceptable (provide with safty packing)
5.What's the delivery time?
According to different method and country , express will be 6~15 days
6.How to install and operate?
According to each instruction manual which sent with equipment. ( We also provide after-sale technical support)
7.What's the payment term?
Normally 30% paid by T/T in advance and 70% paid by T/T before shipping by air.Or 99%T/T.Other payment term is negotiable,like Western union.
oil dissipation factor tester





If you have some requests
Please let me know
We will answer
ASAP






所有评论仅代表网友意见,与本站立场无关。