Huazheng Electric Manufacturing (Baoding) Co.,Ltd is one of the most professional 2500a-7500a busbar temperature rise high current test device manufacturers and suppliers in China. Please feel free to buy cheap products made in China here from our factory.
2500A-7500A Busbar Temperature Rise High Current Test Device
| No. | Name | Specification | Picture | |
| 1 | HZDL-2500Q-Temperature rise test system | Current Output System: Utilizes a three-phase current source (0-2500 A). Comprises multiple parallel current source groups; output current per group is independently adjustable. Output phase angles of all groups are strictly synchronized (identical A-phase angle, identical B-phase angle, identical C-phase angle across all groups). Total current applied to the incoming cabinet equals the vector sum of currents from each group. Maximum Output Current: AC Single-phase: 2500 A AC Input Specifications: Connection: 3Φ4W (Three-phase, Four-wire) Voltage: 380 V ±10%, 50 Hz ±2% Input Current: 263 A Output Specifications: Connection: 3Φ4W (Three-phase, Four-wire) Voltage: 0-8 V Current: Split-phase AC 0-2500 A, continuously adjustable (per phase) Capable of three-phase simultaneous output or single-phase output. Supports both manual output and automatic output modes. Capacity: 75 kVA (3 × 25 kVA) Current Stabilization Accuracy: ≤ ±0.5% (of output current value) Display & Setting: Auxiliary Voltmeter: Display: True Color LCD + Digital Meter Resolution: 0.1 V Display Error: ≤ ±0.2% ±1 digit Auxiliary Ammeter: Display: True Color LCD + Digital Meter (5-digit display) Resolution: 0.1 A Display Error: ≤ ±0.2% ±1 digit System Performance: Overall Efficiency: ≥ 90% Dielectric Strength & Insulation: AC 1800 V for 1 minute, Insulation Resistance ≥ 20 MΩ Cooling Method: Natural Convection Cooling (Fanless) Transformer Accuracy Class: 0.2 Protection Class: IP20 Continuous Operation Capability: Yes, supports uninterrupted 24-hour testing. Long-Duration Operating Mode: Designed specifically for extended temperature rise experiments. Temperature Measurement System: Number of Channels: 100 channels Measurement Range: -50°C to +400°C Measurement Accuracy: 0°C to 400°C: ±(Reading × 0.2% + 1)°C -50°C to 0°C: ±(Reading × 0.2% + 2)°C |
2500A Current source
| 1 pcs |
| 2 | Temperature Meter | 100-probs temperature meter, |
| 1 pcs |
| 3 | High current flexible cable | Each 200 square 2m 2500A wire Total 30pcs |
| |
| 4 | Computer | Main host software without Monitor,1 pcs |
| 1 pcs |
| 5 | HZDL-7500Q Temperature rise test system | Current Output System: Adopts a unidirectional three-phase current source (0-7500 A). The system consists of multiple parallel current source groups; the output current of each group is independently adjustable. The output phase angles of all groups are strictly synchronized (i.e., the phase angle for A-phase is identical across all groups, the phase angle for B-phase is identical across all groups, and the phase angle for C-phase is identical across all groups). The total current applied to the incoming cabinet under test equals the vector sum of the currents from each group. Maximum Output Current: AC Single-phase: 7500 A AC Input Specifications: Connection: 3Φ4W (Three-phase, Four-wire) Voltage: 380 V ±10%, 50 Hz ±2% Maximum Input Current: 263 A Output Specifications: Connection: 3Φ4W (Three-phase, Four-wire) Open Circuit Voltage: 0-8 V Output Current: Split-phase AC 0-7500 A (Per phase, independently adjustable) Supports three-phase simultaneous output or single-phase output modes. Supports manual output and automatic output control modes. Output Capacity: 225 kVA (3 × 75 kVA) Current Stabilization Accuracy: ≤ ±0.5% (of output current value) Display & Setting: Auxiliary Voltmeter: Display: True Color LCD + Digital Meter Resolution: 0.1 V Display Error: ≤ ±0.2% ±1 digit Auxiliary Ammeter: Display: True Color LCD + Digital Meter (5-digit display) Resolution: 0.1 A Display Error: ≤ ±0.2% ±1 digit System Performance: Overall Efficiency: ≥ 90% Dielectric Strength & Insulation: AC 1800 V for 1 minute, Insulation Resistance ≥ 20 MΩ Cooling Method: Natural Convection Cooling Transformer Accuracy Class: 0.2 Protection Class: IP20 Continuous Operation Capability: Supports 24-hour uninterrupted testing (suitable for long-duration temperature rise tests). Long-Duration Operating Mode: Specifically designed for extended temperature rise experiments. Temperature Measurement System: Number of Channels: 100 channels Measurement Range: -50°C to +300°C Measurement Accuracy: 0°C to 300°C: ±(Reading × 0.2% + 1)°C -50°C to 0°C: ±(Reading × 0.2% + 2)°C |
| 1 pcs |
| 6 | Temperature Meter | 100-probs temperature meter |
| 1 pcs |
| 7 | High current flexible cable | Each 300square 2m 7500A wire Total 75pcs |
| |
| 8 | Computer | Main host software without Monitor,1 pcs |
| 1 pcs |
| 9 | Temperature measuring line | 5M | 100pcs | |
| 10 | Power cable | 3M | 4pcs |











7500A Current source











所有评论仅代表网友意见,与本站立场无关。