HZYDP-30KV High Voltage VLF Hi Pot Tester
Technical parameters
ain parameters of series products are shown in Table 1
| Model | Peak Voltage | Measuring Range | Weight | Purpose |
| VLF-30/1.1 | 30kV | ≤1.1μF @ 0.1Hz | Controller: 4kg Booster: 25kg | Cables, generators with voltage of 10kV and below |
| ≤2.2μF @ 0.05Hz | ||||
| ≤5.5μF @ 0.02Hz | ||||
| VLF-50/1.5 | 50kV | ≤1.5μF @ 0.1Hz | Controller: 5kg Booster: 35kg | Cables, generators with voltage of 20kV and below |
| ≤3.0μF @ 0.05Hz | ||||
| ≤7.5μF @ 0.02Hz | ||||
| VLF-80/1.1 | 80kV | ≤1.1μF @ 0.1Hz | Controller: 5kg Booster: 45kg | Cables, generators with voltage of 35kV and below |
| ≤2.2μF @ 0.05Hz | ||||
| ≤5.5μF @ 0.02Hz |
Table 1 Main Technical Parameters of VLFS Series Ultra-low Frequency High-voltage Generator
★ Power supply: 220V±10%, 50±5%Hz
Note: When a portable generator is used for supplying power, it is required that output voltage and frequency of the generator shall be stable (generally it is required that power shall be greater than 3 kW, the frequency shall be 50 Hz, and voltage shall be 220V±5%), otherwise some assistance measures shall be used to stabilize output of the generator.
★ Output voltage precision:
Degree of instability for peak value of output high voltage: ≤1%
Degree of instability for frequency of output voltage: ≤3%
Distortion rate of output voltage waveform: <5%
★ The instrument has the function of not burning the booster and the mainframe in case of power failure and sudden shutdown during the operation.
★ Service environment: Temperature: -100C~+400C, humidity: ≤85%RH
★Description of testing range:
1. The capacitance of the tested product shall not exceed the maximum rated capacitance of the instrument, and the value is as shown in Table 1;
2. If the capacitance of the tested product is too low, the waveform would be affected. If it is lower than 0.05µF, the instrument would not output normally, so that the auxiliary device (optional) provided by the company can be adopted.
3. For capacitance estimation of common electrical equipment, see Table 2 and Table Table 2 Single-phase to Ground Capacitance of Different Types of Generators
|
| Turbo-generator | Hydro Generator | |||||
| Generator capacity (MW) | 200 | 300 | 600 | 85 | 125-150 | 300 | 400 |
| Single phase to ground capacitance (µF) | 0.198 | 0.18-0.26 | 0.31-0.34 | 0.69 | 1.8-1.9 | 1.7-2.5 | 2.0-2.5 |
Quality Assurance
(1) This instrument is manufactured in strict accordance with national standards and corporate standards, and each instrument has undergone strict factory inspection.
(2) This instrument enjoys a warranty of one year. During this period, if quality is lower than the characteristic requirements due to manufacturing reasons, the company will provide repair for free.
(3) During the lifetime of the instrument, the company will provide related services such as instrument maintenance, user training, and software upgrades for life.
(4) If you find a problem during use, please contact our company in time, and we will take the most convenient way to provide services according to the situation.