HZJY-10K-I High Voltage Insulation Tester Price 10kV Electrical Insulation Resistance Test Device

Brief description
Intelligent insulation resistance tester adopts embedded industrial single-chip real-time operating system, with five kinds of voltage output levels (500V, 1000V, 2500V, 5000V, 10000V), large capacity, strong anti-interference, AC and DC, simple operation, automatic calculation Insulation index (absorption ratio, polarization index), various measurement results have the characteristics of anti-power-down function. It is an ideal test instrument for measuring insulation resistance of large-capacity transformers, transformers, generators, high-voltage motors, power cables, and lightning arresters.
Range accuracy | 500V | 1000V | 2500V | 5000V | 10000V |
Unspecified | <> | <> | <> | <> | <> |
5% | 100k-10G | 100k-20G | 100k-100G | 100k-100G | 100k-200G |
20% | 10G -100G | 20G-200G | 100G-1T | 100G-1T | 200G-2T |
Unspecified | > 100G | > 200G | > 1T | > 1T | > 2T |





Introduction Of Instrument
● The Front Panel Description

number | Description | number | Description |
1 | AC plug | 2 | AC ON |
3 | Test Port(E、G、L) | 4 | LCD display |
5 | Key |
● Key and function
Key numbered from left to right, the first for a total of five off down the power Key.
key number | Description |
1 | Press the switch on button startup, shutdown condition |
2、3、4 | functional key |
5 | The TEST key, press and hold 1 s TEST, then stop (enter the Settings menu is invalid) |














所有评论仅代表网友意见,与本站立场无关。