HZJB-1600B 6 Phase Protection Relay Test Kit
Product Overview
HZJB-1600B relay protection tester is designed according to the relevant technical specifications of "DL/T 624-2010 Technical Conditions for microcomputer relay protection test Device", and based on the IEC61850 communication standard system, using advanced computer technology to realize the relay protection test device.
Equipped with high-performance power amplifier and based on the powerful PowerPC+X86 platform, the product adopts modular design, with powerful, high precision, small size, light weight characteristics, can realize the function and performance of the relay protection device, measurement and control device test, suitable for power plants, substations, all kinds of scientific research units and equipment manufacturing enterprises
Manual test and automatic test dual mode
Manual test
“HZJB-1600B Relay Protection Tester"provides a variety of general test modules, protection test modules and special test modules, providing perfect test solutions for various types of secondary equipment in substation, including relay protection devices and other safety automatic devices. At the same time, it adopts the engineering configuration interface and configuration process similar to the intelligent substation SCL configuration tool, which conforms to the testing habits of the operators, and provides various types of graphics and forms for displaying the test progress and test results, greatly improving the efficiency of the test.
Automatic test
“HZJB-1600B Relay Protection Tester"adopts template-based management scheme to manage automatic test solutions. A test template can contain multiple test items. Each test template is configured for a type of protection. After the template configuration is complete, the user does not need to perform other manual settings, and can complete the automatic test of all test items with one key click Start, and automatically give the test results. Because it is a test template configured for a certain protection device, the template can be used for automatic testing of other types of protection without reconfiguration, improving the reuse rate and test efficiency of the automatic test template.
| Power supply | Power dissipation | <2000VA |
| Ac power supply | 220V±20%(47~63Hz) | |
| Dc power supply | 200~380 VDC | |
| AC voltage source output | Measuring range | 6×125 V,125V/60VA per channel |
| Accuracy | 0.2~2V,±2mV;2V~130V,±0.05% | |
| Resolution | 1mV | |
| AC voltage source output | Measuring range | 6×30A,30A/300VA per channel |
| Accuracy | 0~500mA,±1mA; 500mA~30A,±0.05% | |
| Resolution | 1mA | |
| Output phase | Range | 0~360° |
| Accuracy | <±0.001Hz(0~65Hz) <±0.02Hz(450~1200Hz) | |
| Resolution | 0.001 Hz | |
| DC voltage source output | Range | -175~+175V(L-N),1*0~350V(L-L) |
| Accuracy | 0.1% | |
| DC voltage source output | Range | 6 channels ,each 0~30A/250VA |
| Accuracy | 0.1% | |
| Independent auxiliary DC | 110/220VDC is switchable, power no less than 100W | |
| Precision | 0.5% | |
| Synchronous interface | Number | GPS/BD ANT 1 piece;IRIG-B/PPS optical signal 2 pieces:1 time synchronization and 1 time service;IRIG-B/PPS signal 2 pairs:1 pair time synchronization and 1 pair time service;IEEE 1588 1 pair |
| Interface type | GPS/BD ANT,IRIG-B/PPS optical signal;IRIG-B/PPS electric signal;IEEE 1588 | |
| Time measurement | Range | 1ms~9999.999s |
| Accuracy | 1ms | |
| Digital Input | Number | 8 pairs |
| Digital Output | Number | 6 pairs,among them, 2 pairs are fast opening (reaction time ≤0.1ms), which can be added |
| Interrupting capacity | DC250V /0.5A | |
| Wireless connections | Interface type | WIFI,4G |
| Wired connection (Ethernet communication interface) | Number of ports | 2 |
| Interface type | 100 megabit LAN port,RJ45 | |
| Power supply | Supply voltage | AC/DC 220V,Tolerance error:±20% |
| Power supply frequency | 47~65 Hz | |
| Auxiliary power supply | 110V/220V each channel | |
| Analog small signal input (optional) | Number of channels | 12 |
| Interface type | Aviation plug, AC voltage | |
| Analog small signal output (optional) | Number of channels | 12 |
| Interface type | Aviation plug, AC voltage | |
| USB Interface | Number | 3 |
| Working environment conditions | Operating temperature | -10℃~50℃ |
| Humidity | ≤95%,No condensation | |
| Others | On-line interface | RJ45 |