IEC 61869-3 Voltage Transformer On-site Calibration Device
System configuration
| No. | Name | Model No. | Technical Index | Qty |
| 1 | PT Calibrator | HZQB-C | Accuracy: 2.0 Frequency: 50HZ | 1 pc |
| 2 | PT load bank | FY95 | 110V,110/√3V,110/√3V 1.25-158.75VA Frequency: 50HZ | 1 pc |
| 3 | Dual voltage regulation controller | KZX-5KVA | Capacity:5KVA Frequency: 50HZ | 1 pc |
| 4 | Accuracy PT With voltage booster | HZ-S33G3 | 33kV/110V Accuracy:0.05 Frequency: 50HZ | 1 pc |
| 5 | Accuracy PT With voltage booster | HZ-S11G3 | 11kV/110V Accuracy:0.05 Frequency: 50HZ | 1 pc |
| 6 | Primary voltage cables |
|
| 1 set |
1.HZQB-C PT Calibrator

Product Overview
The HZQB-C transformer calibrator can measure the ratio difference, angle difference, admittance, and impedance of various models of CT and PT. The instrument is equipped with a micro printer, and the software is powerful with tables, which can connect to computers and transmit test data.
Technical Index
| Environment | Temperature:5℃-40℃ Relative humidity:<80%(25℃) Altitude:<2500mm Power frequency:50Hz±0.5 Hz Power votlage:220V±5 V |
| Measuring range | In-phase components(%): 0.0001~200.0 Resolution:0.0001 Quadrature components:0.001~700.0 Resolution:0.001 Impedance(Ω): 0.0001~20.0 Resolution:0.0001 Admittance(ms): 0.0001~20.0 Resolution:0.0001 |
| Basic error | In-phase components:ΔX=±(X×2%+Y×2%)±Dx(Class 1 optional) Quadrature components:ΔY=±(X×2%+Y×2%×34.48)±Dy (Class 1 optional) “X”、“Y”——Display value of the instrument “Dx,Dy”——Quantification error of the instrument Dx=2, Dy=5 dial indicator:2.0 class |
| Working range | Current :(1%-149%)In (In =5A) (5%-149%)In (In =1A) Voltage :(5%-149%)Un (Un =100V,150V,100V/) (5%-149%)Un (Un =100V/3) |
| Dimensions(mm) | 410(L)*330(W)* 180(H) |
| Weight(kg) | 5.5 |
Product Features
Display method: Chinese large LCD screen;
Storage function: PT and CT data can store a total of 100000, and can store 1% error data of CT;
Automatic measurement: capable of fully automatic measurement according to regulations, for S-level transformers;
Online function: able to connect with a computer;
Printing function: real-time or query printing;
Measurement range: CT, PT, impedance, admittance;
Automatically determine polarity, wiring, transformer ratio errors, and other indications, effectively ensuring personal and instrument safety.
2.FY95 Voltage Transformer Load Bank

Main features
Lightweight, beautiful appearance, and wide voltage range.
Technical Index
| Environment | Temperature:5—40℃ Humidity:<80%(25℃) Altitude: <1500m |
| Rated capacity | 1.25~158.75VA |
| Voltage range | 20%-120% |
| Primary voltage | 110V,110/√3V,110/3V |
| Power factor | 0.8 ,1.0 |
| Accuracy | ±3%±0.01VA |
| Test voltage | 2kV |
| Rated frequency | 50Hz |
3.KZX-5KVA Dual voltage regulation controller

Product Features
This series of consoles is suitable for voltage regulation control of 0.5-5KVA test transformers. Working principle: By adjusting the output voltage of the autotransformer, the working adjustment within the rated voltage range of the test transformer can be achieved. The console is equipped with a high-voltage output voltmeter and a low-voltage output ammeter, which can easily read out the test voltage value. By using overcurrent protection circuits to reliably protect equipment, the designed timing alarm circuit makes testing more convenient. It has been proven by users that its principle is simple, its structure is compact, its work is reliable, and its use is convenient, making it an ideal equipment for high-voltage testing.
Technical indicators
Input voltage: AC220V
Capacity: 5KVA+300VA
Capable of controlling the flow regulator and pressure regulator separately
With coarse and fine adjustment functions
4.HJ-S11G3 Precision voltage transformer

Product Overview
11kV, 0.05 level voltage transformer is a high voltage level and high accuracy voltage transformer that can be calibrated 11 kV, voltage transformer below 0.2 level. When the secondary voltage is 100V, it can carry a secondary load of 0.25VA.
Technical indicators
1) Rated voltage ratio: 11 kV/100V
2) Rated secondary capacity: 0.2VA, 0.07VA, Cos Ф= one
3) Accuracy level: 0.05
4) The test voltage is 1.2 Un for 1 minute for the primary winding, and 2kV for 1 minute for the secondary winding to ground
5) Rated frequency; 50Hz
5.HJ-S33G3 Precision voltage transformer

Product Features
33kV, 0.05 level voltage transformer is a high voltage level and high accuracy voltage transformer that can achieve calibration of 33kV, 0.2 level and below voltage transformers. It can carry a secondary load of 0.25VA at 100V, fully meeting the calibration requirements of voltage transformers.
Technical indicators
1) Rated voltage ratio: 33KV/100V; 33//100/V
6) Rated secondary capacity: 0.2VA, 0.07VA, Cos Ф= one
7) Accuracy level: 0.05
8) The test voltage is 1.2 Un for 1 minute for the primary winding, and 2kV for 1 minute for the secondary winding to ground
9) Rated frequency; 50Hz

















所有评论仅代表网友意见,与本站立场无关。