HZDL-N2 2000Amp Primary Current Injection Test Case
Tech Data
Input Power Supply: AC:220V·50A,50Hz.
Output Current: AC:2000A·6V or 1000A·12V.
The Range of Primary Current: 0~2200A, Resolution:0.1A;
The Range of Secondary Current: 0~6A; Resolution:0.001A.
Precision: TRUE RMS ±0.5%.
Usage Environment: Temperature -10~40℃,
Relative humidity<80%.
Safety Precautions
1. In order to ensure the safe operation of test, the instrument should be grounded reliably before the test.
2. The power supply voltage should be set as 240V±10%. Do not input 380V power supply into the instrument, or the instrument will be severely damaged.
3. Connecting or disconnecting the test wire is strictly prohibited when the test is conducting.
4. For the test set, the cable cross-section of input power should be greater than 2mm2, and the cable cross-section of high current output connection should be greater than 70mm2, and the cable length of the output connection should be kept as short as possible.
5. Use paralleling output wherever possible, if only the demand of output current is met.
6. Avoid continuous output in a long time.