100kW 3 Phase AC Variable Resistive Load Bank
Technical parameters of load box
Total power | 100KW |
Resistive load | Using special alloy resistors, the resistance error is ±5%. |
Test voltage | AC three-phase 380V/3P4W |
Auxiliary voltage | AC220V/50Hz |
A-phase power gear | 0.5KW*1 、1KW*2 、2KW*2 、3KW*1 、4KW*1 、5KW*2 、10KW*1; 10 power gear in total, 33.5KW。 |
B-phase power gear | 0.5KW*1 、1KW*2 、2KW*2 、3KW*1 、4KW*1 、5KW*2 、10KW*1; 10 power gear in total, 33.5KW。 |
C-phase power gear | 0.5KW*1 、1KW*2 、2KW*2 、3KW*1 、4KW*1 、5KW*2 、10KW*1; 10 power gear in total, 33.5KW。 |
Step power | Three-phase 1.5KW/ single phase 0.5KW |
Power factor | 1 |
Load control | 1P miniature circuit breaker control |
Monitoring function | The local multi-function meter displays the current, voltage, power and other electrical parameters of the test circuit, and the temperature of the air outlet. |
Cooling method | Forced air cooling, wind in from the right and wind out from the left. |
Working environment | 1. Ambient temperature: -20℃~50℃ 2. Relative humidity: The daily average value is not more than 95%, and the monthly average value is not more than 90%. 3. Altitude: ≤2500m 4. Installation conditions: For outdoor use, the air is free of corrosive or flammable gas, water vapor and other obvious pollution, and there is no severe vibration. 5. Protection level: IP21. |
Physical dimension | Approximate width 750*depth 950*height 2000mm |
Weight | About 300KG |
Cabinet color | The metal shell is uniformly sprayed and the color of the cabinet is white. |