HZ-20A-I Handheld Surge Arrester Characteristics Test Set
I.Overview
Handheld zinc oxide arrester tester is a special instrument used for field and laboratory testing of various electrical parameters of arresters. This instrument adopts advanced technologies such as microcomputer sampling and control, and can measure the full current, third harmonic, resistive current, resistive current peak value, capacitive current, active power, etc. of zinc oxide arrester under power frequency voltage. And display voltage, current waveform and print out test data. Using large-screen LCD display, Chinese characters menu prompts operation, making the man-machine exchange function stronger, and at the same time providing on-site waveform display. The instrument has the characteristics of simple wiring, high measurement accuracy and strong reliability. The instrument is small in size, light in weight, and adopts an integrated design, which is easy to carry and operate in the field.
II.Technical parameters
1. Voltage and current parameters::
Measurement item | Test range | Test accuracy |
Full current | 0-20mA | ±(reading×5%+5uA) |
Resistive current | 0-20mA | ±(reading×5%+5uA) |
Capacitive current | 0-20mA | ±(reading×5%+5uA) |
Current harmonics | 0-20mA | ±(reading×10%+10uA) |
Reference voltage | Maximum 250V RMS | ±(reading×5%+0.5V) |
Voltage harmonics | Maximum 250V RMS | ±(reading×10%) |
2. Working temperature: -10℃~40℃
3. Ambient humidity: ≤85% without condensation
4. Storage temperature: -20℃~50℃
5. Dimensions: Host 360*290*170(mm),box 425*335*210(mm)
6. Instrument weight: Host 1.6KG, box 8KG
7. Length of test line: standard 10 meters, the length can be customized
III.Precautions:
1. In order to use the instrument safely and correctly, please read the instruction manual carefully. Wire and operate according to this manual.
2. Please enter the correct setting parameters before the test starts.
3. The instrument can only be used for low voltage and small current testing, and all leads must be kept away from high voltage.
5. During the test, it is not allowed to remove the test leads.
6. The memory can store 200 measurement results, and the earliest record will be overwritten when more than 200 times, please pay attention to copy or export to U disk in time.
7. The host and wireless collector can work while charging. Please charge the battery once a month to prevent the battery from running out of power for a long time.
8. There are 100mA fuses on the wires connected to the PT voltage. Do not replace them with fuses or wires of other specifications.
9. If the instrument fails, the test object will not be damaged. It is not allowed to start maintenance and dismantle without our company's permission. Please contact our company's after-sales service.














所有评论仅代表网友意见,与本站立场无关。