UNI-T UT283A Single Phase Power Quality Analyzer True RMS USB Interface
Features
| Specifications | Range | Best Accuracy | |||
| Model | UT283A | ||||
| Voltage (V) | 10V~1000V AC/DC | ±0.5% Udin | |||
| AC Current (A) | 10A/100A/1000A | ±0.5% f.s. | |||
| Frequence (Hz) | 40~70Hz | ±50mHz | |||
| Power (W) | >15% S | ± 1 %S | |||
| Power factor | 0~1.0 | ± 0.02 | |||
| Energy (Wh) | 0~9999MWh | ± 1.5 %rdg | |||
| Crest factor | 1.0 to 10.0 | ±5 % | |||
| Voltage harmonics or Inter harmonics | Um ≥ 3% Udin(1~51th,step 0.5th) | ±5% Urms | |||
| Um ≤ 3% Udin(1~51th,step 0.5th) | ±0.15% Udin | ||||
| Current harmonics or Inter harmonics | Im ≥ 10% I f.s(1~51th,step 0.5th) | 5% Irms | |||
| Im ≤ 10% I f.s(1~51th,step 0.5th) | ±0.5% f.s. | ||||
| Power harmonics | (1~51th,step 1th) | Calculated based on voltage and current amplitude and phase accuracy | |||
| Transients | ±(2000 V~ 6000 V Peak), Fsample=2MHz | ±5% Rdg.±5%Fs | |||
| Dips Swell & Interrupt | 0~1000V AC | Udin± 1 % | |||
| AC Inrush Current (A) | 10A/100A/1000A | ±1%f.s | |||
| Resistance (Ω) | 600Ω/6KΩ/60KΩ/600KΩ/6MΩ/60MΩ | ±(1.0%+3) | |||
| Capacitance (F) | 60nF/600nF/6μF/60μF/600μF | ±(4 %+20) | |||
| Features | |||||
| True RMS | √ | ||||
| Harmonic Analysis | Up to 51th | √ | |||
| Flick Measure | 10 Minutes PST and PLT value | √ | |||
| Voltage Ratio | √ | ||||
| Current Ratio | √ | ||||
| Event Capture | √ | ||||
| Trend Capture | √ | ||||
| Data Logging | 8GB | √ | |||
| USB Interface | √ | ||||
| Backlight Adjustment | √ | ||||
| Low Battery Indication | √ | ||||
| Input Protection | |||||















所有评论仅代表网友意见,与本站立场无关。