Meter Output: 0 – 1 mA meter output for loads up to 750 ohms
b. Proportional Output: Proportional to input frequency range, configurable as:
i. 4 – 20 mA into maximum 1K load
And one of either:
ii. 0 – 5 VDC into 20K load or higher or
iii. 0 – 10VDC into 20K load or higher
Note that the 4 – 20 mA output is isolated but the 0 – 5 VDC & 0 – 10 VDC outputs are referenced to input supply ground. 0 – 1mA output is referenced to separate ground (Meter Output).
c. Supply Output: Regulated +12 VDC ±5%; 40 mA for active pickup
power.
d. Repeater Output: Square wave 12 V peak-to-peak, 10 mA max load,
Zero based, positive going.
e. Response Time: 50 milliseconds, 10% to 90% rise (standard)
Full-scale frequency ranges below 80 Hz are proportionally slower.
10milliseconds, 10% to 96% rise (standard)
Full-scale frequency ranges below 300Hz are proportionally slower. For 10mSec response time the input frequency signal must be noise free.