HZ-3140A 40A Transformer DC Winding Resistance Meter
HZ-3140 40A Transformer DC Resistance Meter introduction
Winding resistance of the transformer will test the project of a transformer manufacturing semi-finished products,finished appearance test,installation, testing and transfer of power sector preventive trials , which can effectively find the transformer coil selection, welding, loose joints, missing stocks, disconnection and other manufacturing after the existence of hidden defects and running.
HZ-3140 40A Transformer DC Resistance Meter Functions and Features
Large output current, wide measuring range, small size, light weight, simple operation
High test speed, high precision, retest good, strong anti-jamming capability
With perfect protection circuit, high reliability
With discharge audible alarm function, clear discharge instructions , to reduce misuse
HZ-3140 40A Transformer DC Resistance Meter technical Parameters
Output currents 40A 20A 10A 5A 2.5A
Measure range 40A:100µΩ~500mΩ 20A:250µΩ~1Ω
10A:500 µΩ ~2Ω 5A:1mΩ~4Ω
2.5A:2mΩ~8Ω
Resolution 0.1µΩ
Accuracy ± (0.2%+2words)
Dimensions 390mm×235mm×245mm
Instrument weight 12kg
HZ-3140 40A Transformer DC Resistance Meter Conditions of Use
Ambient temperature -10℃~50℃
Humidity ≤85%RH
Power Supply AC220V ± 10%
Power frequency 50 ± 1Hz
Instrument panel
~220V:Power switch, machine power input, AC socket, safety and switch.
Earthed: Earthed terminal,used for whole instrument earthing,for safety protection.
RST:machine restore the initial status,pre-set the current output.
Circle: select menu.
SEL:Setup the current after the tester was reset.
S-up key:press the key after selecting the current; The microcomputer control to realize all testing process.
I+、 I-:Current output terminals ,I+ is the positive current; I- is the negative current.
V+、V-:Voltage input terminals, V+ is the positive voltage;V- is the negative voltage.
RS232: Universal series interface, can controlled by computer.
USB: Can output the testing results to USB.