20% Power Good Material Save Double-Stage Transformer Oil Filtration Machine
Application of Transformer Oil Filtration Plant:
The transformer oil filtration machine is applied to purify the unqualified transformer oil, mutual inductor oil, switch oil and other insulation oil.,which can quickly and effectively remove water, gas and impurities from insulating oil and transformer oil.
Especially for large transmission and transformation voltage equipment above 110KV and national main transformer network in areas above 500 meters above sea level.
Technical Parameter
Product Specifications | ||||||||
Item | Unit | ZJA-30 | ZJA-50 | ZJA-75 | ZJA-100 | ZJA-150 | ZJA-200 | ZJA-300 |
Flow rate | L/H | 600 | 1200 | 1800 | 3000 | 4500 | 6000 | 9000 |
Vacuum degree | Pa | ≤133 | ||||||
Ultimate vacuum | Pa | ≤7 | ||||||
Working pressure | Mpa | ≤0.5 | ||||||
Working temperature | ℃ | 30 ~ 60 | ||||||
Power supply | 380V/50Hz (or as per requirement) | |||||||
Noise | dB(A) | ≤78 | ||||||
Heating power | kW | 30 | 45 | 54 | 72 | 120 | 144 | 168 |
Total power | kW | 34 | 49 | 60 | 79 | 131 | 159 | 188 |
Inlet&outlet size | mm | 25 | 32 | 42 | 42 | 50 | 50 | 60 |
Advantages
1.The biggest feature of this device is power saving. It is made of high-quality materials, with high operating efficiency and low investment costs.
2.The company's use of recycled oil can retain control of strategic assets. Recycled oil is an asset. The use of regeneration technology eliminates dependence on oil companies to provide alternative supplies and protects them from sharp fluctuations in external market prices.
Working Principle of Transformer Oil Filtration Equipment:
When we turn on the transformer oil filtration machine, start to purify the oil, the oil will come into the primary filter first by the vacuum negative pressure. To purify the bigger particles, normally 80μm;
Then the oil flow through the second filter, normally 20μm;
After that oil will flow into the heater, then into the vacuum tank to dehydration and degassing by the vacuum;
Then the oil will flow into the fine filter, normally 5μm;
The oil comes out or keeps the loop working.
Treatment of Transformer Oil Filtration System:
Oil index after treatment | ||
Breakdown voltage | KV | 75 |
Water content | ppm | 3 ~ 5 |
Gas content | % | ≤0.1 |
Impurity | µm | 1~5 No free carbon |
Maintenance of Transformer Oil Filtration Plant:
After a certain period of running, the machine should be checked to see whether:
The electrical control system is safe and reliable;
The temperature controller is sensitive, reliable and accurate;
Oil seals of the pump shaft are broken with leakage;
There is any blockage with the running system and any abnormal noise with pumps or related motors;
There is an air or oil leakage with the oil running system and at sealing joints;
After every 3000 hours' running, grease shall be replenished to prevent motors from being burnt;
Special vacuum pump oil or lubricating oil N46 should be used for the vacuum pump and oil replaced or replenished if necessary at any time;
If the transformer oil filtration machine will not be used over 1 month, place the machine in a dry environment with the panel door and all valves closed, and the machine properly protected by a covering.